  • 01172.0-00 Enclosure Dual Thermostat NC NO Heat & Cool 0 to 60C
  • 01172.0-00 Enclosure Dual Thermostat NC NO Heat & Cool 0 to 60C

01172.0-00 ZR011 Enclosure Dual Thermostat NC NO Heat & Cool 0 to 60°C

$43.80
SKU:
01172.0-00
Weight:
0.35 LBS
Availability:
In Stock
Current Stock:
13
Quantity:

Product Description

 

  • NC / NO or NO / NO in one unit
  • Separate adjustable temperatures
  • Color coded temperature dials
  • DIN rail mountable

The ZR011 has two separate thermostats in one housing: This allows the independent control of heating and cooling equipment, or signaling equipment.
Thermostat - NC (normally closed): Opens on temperature rise (red temperature dial) - for regulating heaters or for switching signal devices when temperature has fallen below the minimum value.
Thermostat - NO (normally open): Closes on temperature rise (blue temperature dial) - for regulating filter fans, heat exchangers, or for switching signal devices when temperature limit has been exceeded.

Switch temperature difference 12.6°F ± 7°F tolerance (7°K ± 4°K)
Sensor element thermostatic bimetal
Contact type snap-action contact
Service life > 100 000 cycles
Max. switching capacity NC: 10A resistive / 2A inductive @ 250VAC
  NO: 5A resistive / 2A inductive @ 250VAC
  15A resistive / 2A inductive @ 120VAC
  DC 30W (24-72Vdc)
Max. inrush current 16A VAC for 10 seconds
Connection 4-pole terminal, clamping torque 0.5Nm max.: solid wire 14 awg (2.5mm²) / stranded wire (w/ wire end ferrule) 16 awg (1.5mm²)
Housing plastic according to UL94 V-0. light grey
Mounting molded plastic clip for 35mm DIN rail, EN60715
Mounting position vertical
Operating/Storage temperature -49 to +176°F (-45 to +80°C)
Operating / Storage humidity max. 95 % RH (non-condensing)
Dimensions 2.6x2.0x1.8" (67 x 50 x 46mm)
Weight approx. 3.2 oz (90g)
Protection type IP20 
Approvals  UL File No. E164102, CSA, VDE, EAC

  

Part No. Setting range (NC) Setting range (NO) Approvals  CSA VDE EAC 
01172.0-00 0 to +60°C 0 to +60°C UL File No. E164102      
01172.0-01 +32 to +140°F +32 to +140°F UL File No. E164102      
01175.0-00 -10 to +50°C -20 to +80°C UL File No. E164102 CSA VDE EAC
01175.0-01 +14 to +122°F +68 to +176°F UL File No. E164102 CSA VDE EAC
             
Part No. Setting range (NO) Setting range (NO) Approvals      
01176.0-00* 0 to +60°C 0 to +60°C UL File No. E164102 CSA VDE EAC
01176.0-01* +32 to +140°F +32 to +140°F UL File No. E164102 CSA VDE EAC

 *For regulating heat exchangers and fans (e.g LE 019) and as an alarm contact for monitoring the interior temperature of electronic enclosures.